EasyManua.ls Logo

Adtech iMASTER – A1 Series - Dynamic Braking Unit (DBU) and Resistors

Default Icon
198 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A1-User’s Manual
34
5.1.2 Dynamic braking unit (DBU) and Resistors
1) Dynamic Braking Resistor
200V Drive
150% Torque, 5% ED
400V Drive
150% Torque, 5% ED
VFD Model
kW
W
VFD Model
kW
W
A1-032A-2
5.5
20
800
A1-016A-4
5.5
85
800
A1-045A-2
7.5
15
1200
A1-023A-4
7.5
60
1200
A1-064A-2
11
10
2400
A1-032A-4
11
40
2400
A1-076A-2
15
8
2400
A1-038A-4
15
30
2400
A1-090A-2
18.5
5
3600
A1-045A-4
18.5
20
3600
A1-058A-4
22
20
3600
2) Dynamic Braking Unit
Input V
VFD Model
kW
DB Unit Model
kW
Condition for using
3 PHASE
200V
A1-114A-2
22
FBU050-022-2
5
6
150% breaking
10%ED
A1-140A-2
30
FBU100-037-2
4.5
10
A1-170A-2
37
4.5
10
A1-205A-2
45
FBU100-075-2
2.5
10
A1-261A-2
55
2.5
20
A1-310A-2
75
2.5
20
3 PHASE
400V
A1-075A-2
30
FBU100-037-4
12
10
A1-090A-2
37
12
10
A1-110A-4
45
FBU100-075-4
6
10
A1-149A-4
55
6
20
A1-176A-4
75
6
20
A1-217A-4
90
FBU100-090-4
5
26
A1-260A-4
110
FBU100-132-4
3.4
40
A1-296A-4
132
3.4
40

Table of Contents