A1-User’s Manual
66
8.1.10 Start/Stop mode
No.
Name
Change during
operation
Range
Default
Page
21.01
Torque boost mode
X
0. Manual torque boost
1. Automatic torque boost
0
110
21.02
Magnetization time
X
0.0 to 3000 [Sec]
0.0 Sec
110
21.03
Magnetization Level
X
0.0 to 200.0 [%]
30.0 %
110
21.04
Stop mode
O
0. Ramp (Dec)
1. Coast (Free-run)
0
110
21.05
DC current control
(DC brake)
X
0. Disable
1. Enable
0
111
21.06
DC hold frequency
X
0.00 to 10.00 [Hz]
0.50 Hz
111
21.07
DC hold time
X
0.0 to 3000 [Sec]
0.0 Sec
111
21.08
DC hold delay time
X
0.0 to 50.0 [Sec]
0.0 Sec
111
21.09
DC current reference
X
0.0 to 100.0 [%]
10.0 %
111
21.10
Emergency stop mode
O
0. Ramp (Dec)
1. Coast (Free-run)
0
112
21.11
Emergency stop source
O
0. Active
1. Inactive
2. DI1
3. DI2
4. DI3
5. DI4
6. DI5
7. DI6
8. DI7
9. DI8
1
112
21.12
DC current control P gain
O
1 ~ 10000
1000
112
21.13
DC current control I gain
O
0 ~ 10000
500
112