A1-User’s Manual
172
98.05 Voltage gain factor
Range: 20.0 ~ 110.0 % in 0.1 %
Initial value: 100.0 %
The output voltage cannot exceed the input voltage
100 %
F(Hz)
99.02 (Motor rated voltage)
V
70 %
0
98.05 (Voltage gain factor)
98.06 Flux braking function
0: Disable
1: Enable ----- Initial value
It can select to use Flux braking Function
Related Parameters:
'42.10', '98.07'
98.07 Flux braking reference
Range: 100 ~ 140 % in 1
Initial value: 110 %
It can program a Flux braking reference
98.09 Manual torque boost voltage reference
Range: 0.00 ~ 50.00 % in 0.01 %
Initial value: 1.0 %
For Manual Torque Boost mode, program the value in % of an output voltage
It not works in auto torque mode or sensorless mode
Related Parameters:
'21.01', '98.01', '98.10'