Publication 1762-UM001D-EN-P - March 2004
Installing Your Controller 2-5
Power Distribution
There are some points about power distribution that you should
know:
The master control relay must be able to inhibit all machine
motion by removing power to the machine I/O devices when
the relay is de-energized. It is recommended that the controller
remain powered even when the master control relay is
de-energized.
If you are using a dc power supply, interrupt the load side rather
than the ac line power. This avoids the additional delay of
power supply turn-off. The dc power supply should be powered
directly from the fused secondary of the transformer. Power to
the dc input and output circuits should be connected through a
set of master control relay contacts.
Periodic Tests of Master Control Relay Circuit
Any part can fail, including the switches in a master control relay
circuit. The failure of one of these switches would most likely cause
an open circuit, which would be a safe power-off failure. However, if
one of these switches shorts out, it no longer provides any safety
protection. These switches should be tested periodically to assure they
will stop machine motion when needed.
Power Considerations
The following explains power considerations for the micro controllers.
Isolation Transformers
You may want to use an isolation transformer in the ac line to the
controller. This type of transformer provides isolation from your
power distribution system to reduce the electrical noise that enters the
controller and is often used as a step-down transformer to reduce line
voltage. Any transformer used with the controller must have a
sufficient power rating for its load. The power rating is expressed in
volt-amperes (VA).

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1200 and is the answer not in the manual?

Allen-Bradley MicroLogix 1200 Specifications

General IconGeneral
SeriesMicroLogix 1200
TypeProgrammable Logic Controller (PLC)
MountingDIN rail or panel mount
Programming LanguageLadder Logic
Programming SoftwareRSLogix 500
I/O PointsUp to 40
Communication PortsRS-232, RS-485
Memory6 KB user memory
Power Supply24V DC or 120/240V AC
ExpansionSupports expansion I/O modules
Operating Temperature0°C to 55°C (32°F to 131°F)
Dimensions90 mm x 110 mm
Weight0.5 kg (1.1 lbs)

Related product manuals