EasyManuals Logo

Allen-Bradley MicroLogix 1200 User Manual

Allen-Bradley MicroLogix 1200
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
Publication 1762-UM001D-EN-P - March 2004
2-6 Installing Your Controller
Power Supply Inrush
During power-up, the MicroLogix 1200 power supply allows a brief
inrush current to charge internal capacitors. Many power lines and
control transformers can supply inrush current for a brief time. If the
power source cannot supply this inrush current, the source voltage
may sag momentarily.
The only effect of limited inrush current and voltage sag on the
MicroLogix 1200 is that the power supply capacitors charge more
slowly. However, the effect of a voltage sag on other equipment
should be considered. For example, a deep voltage sag may reset a
computer connected to the same power source. The following
considerations determine whether the power source must be required
to supply high inrush current:
The power-up sequence of devices in a system.
The amount of the power source voltage sag if the inrush
current cannot be supplied.
The effect of voltage sag on other equipment in the system.
If the entire system is powered-up at the same time, a brief sag in the
power source voltage typically will not affect any equipment.
Loss of Power Source
The power supply is designed to withstand brief power losses without
affecting the operation of the system. The time the system is
operational during power loss is called “program scan hold-up time
after loss of power.” The duration of the power supply hold-up time
depends on the type and state of the I/O, but is typically between 10
milliseconds and 3 seconds. When the duration of power loss reaches
this limit, the power supply signals the processor that it can no longer
provide adequate dc power to the system. This is referred to as a
power supply shutdown. The processor then performs an orderly
shutdown of the controller.

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1200 and is the answer not in the manual?

Allen-Bradley MicroLogix 1200 Specifications

General IconGeneral
SeriesMicroLogix 1200
TypeProgrammable Logic Controller (PLC)
MountingDIN rail or panel mount
Programming LanguageLadder Logic
Programming SoftwareRSLogix 500
I/O PointsUp to 40
Communication PortsRS-232, RS-485
Memory6 KB user memory
Power Supply24V DC or 120/240V AC
ExpansionSupports expansion I/O modules
Operating Temperature0°C to 55°C (32°F to 131°F)
Dimensions90 mm x 110 mm
Weight0.5 kg (1.1 lbs)