EasyManua.ls Logo

auer HRC70 - Commissioning; Control Panel; Display Screen: Description of Symbols and Their Meaning

auer HRC70
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- INSTALLER 7 & 11kW HRC
70
HIGH TEMPERATURE HEAT PUMP
-
24
4.1.1 - Display screen: description of symbols
and their meaning
9-character
message
Display zone for time
and temperature
Day
4.1 - Control panel
Menu
On / O
Clock
settings
DialDisplay screen
Symbol Meaning
Summer mode in progress
Heat pump running
(compressor and fan running)
De-icing in progress
Electrical back-up is running
Boiler back-up request
Heat Pump circulator pump running
Heating circuit 1 circulator pump running
Heating circuit 2 circulator pump running
Domestic hot water production in progress
Setting / setting display
Time or programme is being set
"Comfort" mode
"Economy" mode
"Frost protection" mode
"Holiday" mode
4 - COMMISSIONING
• All work carried out on the water circuits and electrical
installations must be carried out by a quali ed professional and
in accordance with current rules and regulations.
• Fill the installation with water and treat the water.
• Purge the heating circuits (open the air valves situated on the
highest points of the installation until all trapped air has been
released).
• Check that all circuits are properly sealed.
• Check that the power supply voltage is correct at the mains
switch.
• Check that all hydraulic connections have been properly
tightened and that there are no leaks.
• Check that all the valves are open, that there is water in the
heating circuit and that nothing is stopping the water from
circulating freely in the heat exchanger and the hydraulic circuit.
• Check that the sludge valve is correctly  tted and that nothing is
blocking its screen  lter.
• Once all of these checks have been carried out, switch the
appliances on.
• Configure the installation.
The appliance is pre-con gured for the following system:
- 17 kW Heat Pump
- Heat Pump without back-up
(neither boiler or electrical)
- 1 radiator circuit
- 1room thermostat to control radiator circuit
temperature
If necessary, this con guration can be modi ed using the
"Installer" menu.
N.B: Frost protection for the Heat Pump
When the Heat Pump is switched o (temporarily or de nitively),
and the temperature of the outgoing water from the Heat Pump
falls below 5°C, the circulator pump starts up and will only stop
running when the water temperature reaches 11°C.
The installation must NEVER be switched
on WITHOUT WATER in the heating circuit

Table of Contents