EasyManua.ls Logo

auer HRC70 - A1.2 - HRC 70 Pilot; A2 - Technical Specifi Cations; A2.1 - HRC 70 Heat Pump

auer HRC70
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- INSTALLER 7 & 11kW HRC
70
HIGH TEMPERATURE HEAT PUMP
MANUAL -
53
A1.2 - HRC
70
Pilot
A2 - Technical speci cations
A2.1 - HRC
70
Heat Pump
HRC
70
7 HRC
70
11 HRC
70
11
Single phase
151291
Single phase
151231
Three phase
151241
Normative data
EN 14511
Heat output
(A7W35)
7.1 kW 10.1 kW 10.1 kW
Power consumption
(A7W35)
1.78 kW 2.6 kW 2.6 kW
COP (A7W35)
4 3.9 3.9
Heat output
(A2W35)
6 kW 8.4 kW 8.4 kW
Power consumption
(A2W35)
1.82 kW 2.6 kW 2.6 kW
COP (A2W35)
3.3 3.25 3.25
Heat output
(A-7W65)
4 kW 6 kW 6 kW
Max. water temperature
R290 refrigerant
Outdoor air temperature
range
Single phase
400V three
phase
Maximum start-up current
15 A 21 A 9 A
Soft starter
NO
Main circuit breaker
16 A
Min power cable width
5 x 2.5 mm²
Main body
Dimensions (H x L x D)
Weight without water
108 kg 115 kg 115 kg
Nominal water flow rate
1350 L/h 1550 L/h 1550 L/h
Hydraulic connection
1"
Max. hydraulic pressure
Condensates drainage pipe
Ø
Air flow rate
3500 m
3
/ h 4500 m
3
/ h 4500 m
3
/ h
Adjustable silent blocks
Overall noise levels in
accordance with EN 12102
1300 mm x 700 mm x 400 mm
3.1 bar
20 / 25 mm
included
1'' / 26/34 male
230V single phase
included
Monobloc Heat Pump
with hydraulic connection
70°C
0.75 kg
32 A
3 x 6 mm²
at 1m 58.2 dB(A)
-20°C to +40°C
steel
Heating
circuit
return
Heating
circuit
supply
Water
outlet
Water
inlet

Table of Contents