- INSTALLER 7 & 11kW HRC
70
HIGH TEMPERATURE HEAT PUMP
MANUAL -
59
A7 - Performance tables
A7.1 - HRC
70
7 kW Heat Pump
Outdoor
temperature
Supply
temperature
Thermal
power
output
Electrical
power
consumption
COP
Air Water Max. Max.
15°C 35°C 12.4 2.4 5.3
15°C 45°C 11.9 3.0 4.0
15°C 55°C 11.4 3.6 3.2
15°C 65°C 10.7 4.1 2.6
7°C 35°C 10.1 2.6 3.9
7°C 45°C 9.9 2.9 3.4
7°C 55°C 9.5 3.4 2.8
7°C 65°C 9.0 3.9 2.3
0°C 35°C 8.2 2.6 3.2
0°C 45°C 7.9 2.8 2.8
0°C 55°C 7.6 3.2 2.4
0°C 65°C 7.3 3.7 2.0
-7°C 35°C 6.9 2.4 2.9
-7°C 45°C 6.7 2.7 2.5
-7°C 55°C 6.4 3.1 2.1
-7°C 65°C 6.1 3.4 1.8
-15 °C 35°C 5.9 2.2 2.7
-15 °C 45°C 5.8 2.5 2.3
-15 °C 55°C 5.5 2.9 1.9
-15 °C 65°C 5.2 3.0 1.7
-20 °C 35°C 5.2 2.4 2.2
-20 °C 45°C 5.1 2.4 2.1
-20 °C 55°C 4.8 2.6 1.8
-20 °C 65°C 4.3 2.5 1.7
A7.2 - HRC
70
11 kW Heat Pump
Outdoor
temperature
Supply
temperature
Thermal
power
output
Electrical
power
consumption
COP
Air Water Max. Max.
15°C 35°C 8.4 1 .6 5.1
15°C 45°C 8.1 2 .1 3.9
15°C 55°C 7.7 2 .5 3.1
15°C 65°C 7.3 2 .8 2.6
7°C 35°C 7.1 1 .8 4.0
7°C 45°C 6.7 2 .0 3.3
7°C 55°C 6.4 2 .4 2.7
7°C 65°C 6.1 2 .7 2.2
0°C 35°C 5.6 1 .7 3.3
0°C 45°C 5.4 1 .9 2.8
0°C 55°C 5.2 2 .2 2.3
0°C 65°C 4.9 2 .5 2.0
-7°C 35°C 4.7 1.6 2.9
-7°C 45°C 4.5 1.9 2.4
-7°C 55°C 4.4 2.1 2.1
-7°C 65°C 4.2 2.3 1.8
-15°C 35°C 4.0 1.5 2.6
-15°C 45°C 3.9 1.8 2.2
-15°C 55°C 3.8 2.0 1.9
-15°C 65°C 3.5 2.1 1.7
-20°C 35°C 3.5 1.8 2.0
-20°C 45°C 3.4 1.7 2.0
-20°C 55°C 3.3 1.8 1.8
-20°C 65°C 2.9 1.8 1.6
C7
When using a pure product that needs
to be diluted with water, mix the water,
anti-freeze and inhibitor together outside before
putting it into the installation.
RENDERING THE WARRANTY NULL & VOID
Any deterioration in the condition of the
appliances which is due to unsuitable
quality of  lling water and / or corrosion in the
absence of treatment products as described
above and / or improper degassing of the
installation will result in the warranty being
rendered null and void.
Regularly check the Ph levels and % of
glycol in the installation
Never top up glycol in your installation
without measuring the Ph to check that the
drop in the glycol % is not due to deterioration
in the glycol.
When the Ph is acidic (<7) replace all of the
glycol after having drained and rinsed the
installation beforehand.