When using a pure product that needs
to be diluted with water, mix the water,
anti-freeze and inhibitor together outside before
putting it into the installation.
RENDERING THE WARRANTY NULL & VOID
Any deterioration in the condition of the
appliances which is due to unsuitable
quality of lling water and / or corrosion in the
absence of treatment products as described
above and / or improper degassing of the
installation will result in the warranty being
rendered null and void.
• Regularly check the Ph levels and % of
glycol in the installation
• Never top up glycol in your installation
without measuring the Ph to check that the
drop in the glycol % is not due to deterioration
in the glycol.
• When the Ph is acidic (<7) replace all of the
glycol after having drained and rinsed the
installation beforehand.