- INSTALLER 7 & 11kW HRC
70
HIGH TEMPERATURE HEAT PUMP
-
28
Use Parametre Function Unit Operating range
0
= circulator pump runs constantly
1
= circulator pump controlled
2
= circulator pump runs constantly
even with no heating request
Heating curve parametre
PAR.207
Max. heat pump water temperature °C
PAR.208
to 70°C
70
C
Heating curve parametre
PAR,208
Min. heat pump water temperature °C
20°C to
PAR.207
30
C
Heating curve parametre
PAR.209
Max. outdoor temperature °C
15 to 25
C 20 C
Heating curve parametre
PAR.210
Min. outdoor temperature °C
20 to 0 C 10 C
Difference between target temperature and
maintained temperature
PAR.213
To lower heating curve in
ECO mode periods
K
0K to PAR.214 10K
To lower heating curve
in frost protection mode periods
For heating circuit(s) only
PAR.215
Summer / winter mode time delay hour
0 to 48h 12h
For heating circuit(s) with
temperature control
Heating advance when switching from
"Holiday" mode to "Comfort" mode
0
= No operation authorised
1
= heat pump level 1 authorised
2
= heat pump level 2 authorised
4
= heat pump authorised
and level 1
electrical back-up
5 = heat pump and levels 1
✣
2
electrical backup authorised
6
= Authorised to
operate fully
7
= Boiler authorised only
0
= No operation
authorised
1
= heat pump level 1 authorised
2
= heat pump level 2 authorised
4
= heat pump authorised
and level 1
electrical back-up
5 = heat pump and levels 1
✣
2
electrical backup authorised
6
= Authorised to
operate fully
7
= Boiler authorised only
If there is a domestic water sensor:
Differential sanitary heat demand
If there is a domestic water aquastat:
Heat pump target temperature
DHW sharing
0
= DHW heated as priority
1
= Heating time shared between
DHW and heating
Anti-legionellosis cycle
(lDHW is heated to 6°C every X days at 10pm)
days
0
= DHW heated as priority
0
Differential between heat pump target
temperature and swimming pool target
tempertaure (a gap which fixes the
heat pump target temperature above the
swimming pool target temperature)
Swimming pool heating advance before
leaving "Holiday" mode
days
from
0
= no advance
to
7
= 7 days
1 day
PAR.224
Number of recording sequences per USB file
1 to 255 sequences
(of 128mn)
255
PAR.225
Data recording period mn
1 to 240 1
PAR.230
Choice of compressor
0 ; 1 or 2 0
Remove electrical bridge
(HP/HC) from hydro-electronic
control and connect HP/HC
electricity provider contact
*If parametres
PAR.217
and
PAR.218
are both activated at the same time, the lowest authorisation level will be used on both inputs in case of load shedding
s
Authorisation level for stopping heat pump
and electrical back-up from operating during
peak time
( DEL input)
Remove electrical bridge
(HP/HC) from hydro-electronic
control and connect the loast
shedding contact
Swimming pool circuit on
circuit 1 in addition to the
heating circuit and swimming
pool kit connected to the hydro-
electronic control
Circuit 2: domestic water circuit
with domestic water sensor
(circuit 1 must be a radiator
circuit) or deactivated
Authorisation level for stopping heat pump
and electrical back-up from operating during
peak time
( HP / HC input)
Heating circulation controlled by the room
temperature controller