Add a Serial Remote I/O Master/Slave Module
In addition to the I/O located in the local base, adding remote I/O can be accomplished via a
shielded twisted-pair cable linking the master CPU to a remote I/O base. The methods of
adding serial remote I/O are:
• DL240 CPUs: Remote I/O requires a remote master module (D2–RMSM) to be installed in the
local base. The CPU updates the remote master, then the remote master handles all communication
to and from the remote I/O base by communicating to a remote slave module (D2–RSSS) installed
in each remote base.
• DL250–1 and D2–260 CPU: The CPU’s comm port 2 features a built-in Remote I/O channel. You
may also use up to 7 D2–RMSM remote masters in the local base as described above (you can use
either or both methods).
Remote I/O points map into different CPU memory locations, therefore it does not reduce
the number of local I/O points. Refer to the DL205 Remote I/O manual for details on
remote I/O configuration and numbering. Configuring the built-in remote I/O channel is
described in the following section.
The figure below shows one CPU base, and one remote I/O channel with six remote bases. If
the CPU is a DL250–1 or DL260, adding the first remote I/O channel does not require
installing a remote master module (use the CPU’s built-in remote I/O channel).
DL205 User Manual, 4th Edition, Rev. B
4–26
Chapter 4: System Design and Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
DL230 DL240 DL250–1 DL260
Maximum number of Remote Masters supported in the local
CPU base (1 channel per Remote Master)
none 2 7 7
CPU built-in Remote I/O channels none none 1 1
Maximum I/O points supported by each channel none 2048 2048 2048
Maximum Remote I/O points supported none Limited by total references available
Maximum number of remote I/O bases per channel(RM–NET) none 7 7 7
Maximum number of remote I/O bases per channel (SM–NET) none 31 31 31
230
240
250-1
260
ý
þ
þ
þ
Remote Slaves
Maximum of
7 remote bases
per channel
Remote Masters
Masters can go in any slot except next to CPU.
Allowable distance is from farthest slave to the remote master.
Maximum of:
7 per CPU base (DL250-1 & DL260)
(for DL250-1 & DL260 the bottom port of
the CPU can serve as an eighth master)
2 per CPU base (DL240)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com DirectLOGIC DL205 Series and is the answer not in the manual?

Automationdirect.com DirectLOGIC DL205 Series Specifications

General IconGeneral
BrandAutomationdirect.com
ModelDirectLOGIC DL205 Series
CategoryController
LanguageEnglish

Related product manuals