Chapter 2: Installation, Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Base Wiring Guidelines
Base Wiring
The diagrams show the terminal
connections located on the power supply
of the DL205 bases. The base terminals
can accept up to 16 AWG. You may be
able to use larger wiring depending on
the type of wire used, but 16 AWG is the
recommended size. Do not overtighten
the connector screws; the recommended
torque value is 7.81 ld-in (0.882 N•m).
NOTE: You can connect either a 115 VAC or 220 VAC supply to the AC terminals. Special wiring or jumpers
are not required as with some of the other DirectLOGIC. products.
WARNING: Once the power wiring is connected, install the plastic protective cover. When the cover is
removed there is a risk of electrical shock if you accidentally touch the wiring or wiring terminals.
125 VDC Base Terminal Strip12/24 VDC Base Terminal Strip
G
LG
12 – 24 VDC
+
–
115 – 264 VDC
G
24 VDC OUT,
0.3A
–
+
LG
–
+
110/220 VAC Base T erminal Strip
85 – 264 VAC
G
24 VDC OUT,
0.3A
LG
+
DL205 User Manual, 4th Edition, Rev. B
2–13

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com DirectLOGIC DL205 Series and is the answer not in the manual?

Automationdirect.com DirectLOGIC DL205 Series Specifications

General IconGeneral
BrandAutomationdirect.com
ModelDirectLOGIC DL205 Series
CategoryController
LanguageEnglish

Related product manuals