DL205 User Manual, 4th Edition, Rev. B
2–33
Chapter 2: Installation, Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
D2-08NA-1, AC Input
Optica l
COM
Isolator
INP UT
110 VAC
V+
To LE D
Internal module circuitry
COM
C
C
0
1
2
3
4
5
6
7
Internally
conne cted
110 VAC
0
2
4
6
8
0
10 20 30 40 50 55
Ambient Tempe rature (˚C/˚F )
32
50 68 86 104 122 131
C˚
F˚
Poi nts
C
C
0
4
1
5
2
6
3
7
80-132VAC
10-20mA
D2--08NA-1
IN 1 1 0
D 2 -- 0 8 N A -- 1
VAC
0
1
2
3
4
5
6
7
50/60Hz
Line
Derating Chart
D2-08NA-1 AC Input
Inputs per Module
8
Commons per Module
1
(2 I/O terminal points)
Input Voltage Range
80-132 VAC
Peak Voltage
132 VAC
ON Voltage Level
7
5 VAC minimum
OFF Voltage Level
20 VAC maximum
AC Frequency
47-63 Hz
Input Impedance
12 k@ 60 Hz
Input Current
13 mA @ 100 VAC, 60 Hz
11 mA @ 100 VAC, 50 Hz
Minimum ON Current
5 mA
Maximum OFF Current
2 mA
Base Power Required 5VDC
50 mA
OFF to ON Response
5 to 30 ms
ON to OFF Response
10 to 50 ms
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
2.5 oz. (70 g)