EasyManuals Logo

Automationdirect.com DirectLOGIC DL205 Series User Manual

Automationdirect.com DirectLOGIC DL205 Series
587 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
DL205 User Manual, 4th Edition, Rev. B
2–33
Chapter 2: Installation, Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
D2-08NA-1, AC Input
Optica l
COM
Isolator
INP UT
110 VAC
V+
To LE D
Internal module circuitry
COM
C
C
0
1
2
3
4
5
6
7
Internally
conne cted
110 VAC
0
2
4
6
8
0
10 20 30 40 50 55
Ambient Tempe rature (˚C/˚F )
32
50 68 86 104 122 131
C˚
F˚
Poi nts
C
C
0
4
1
5
2
6
3
7
80-132VAC
10-20mA
D2--08NA-1
IN 1 1 0
D 2 -- 0 8 N A -- 1
VAC
0
1
2
3
4
5
6
7
50/60Hz
Line
Derating Chart
D2-08NA-1 AC Input
Inputs per Module
8
Commons per Module
1
(2 I/O terminal points)
Input Voltage Range
80-132 VAC
Peak Voltage
132 VAC
ON Voltage Level
7
5 VAC minimum
OFF Voltage Level
20 VAC maximum
AC Frequency
47-63 Hz
Input Impedance
12 k@ 60 Hz
Input Current
13 mA @ 100 VAC, 60 Hz
11 mA @ 100 VAC, 50 Hz
Minimum ON Current
5 mA
Maximum OFF Current
2 mA
Base Power Required 5VDC
50 mA
OFF to ON Response
5 to 30 ms
ON to OFF Response
10 to 50 ms
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
2.5 oz. (70 g)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com DirectLOGIC DL205 Series and is the answer not in the manual?

Automationdirect.com DirectLOGIC DL205 Series Specifications

General IconGeneral
BrandAutomationdirect.com
ModelDirectLOGIC DL205 Series
CategoryController
LanguageEnglish

Related product manuals