Port 2 Specifications
The operating parameters for Port 2 on the DL240 CPU are configurable using Aux
functions on a programming device.
• 6-Pin female modular (RJ12 phone jack)
type connector
• K–sequence protocol, DirectNET (slave),
• RS-232, Up to 19.2K baud
• Address selectable (1–90)
• Connect to DirectSOFT, D2–HPP,
DV-1000, HMI, or DirectNET master
• 8 data bits, one start, one stop
• Asynchronous, Half–duplex, DTE
• Odd or no parity
Port 2 Specifications
Port 2 on the DL250-1 and DL260 CPUs is located on the 15-pin D-shell connector. It is
configurable using AUX functions on a programming device. This applies to the DL250 as
well.
• 15-Pin female D type connector
• Protocol: K-sequence, DirectNET
Master/Slave, Modbus RTU Master/Slave,
Remote I/O, (ASCII IN/OUT DL260 only)
• RS-232, non-isolated, distance within 15 m
(approx. 50 feet)
• RS-422, non-isolated, distance within
1000 m
• RS-485, non–isolated, distance within
1000m (DL260 only)
• Up to 38.4K baud
• Address selectable (1–90)
• Connects to DirectSOFT, D2–HPP, operator
interfaces, any DirectNET or Modbus
master/slave, (ASCII devices-DL260 only)
• 8 data bits, one start, one stop
• Asynchronous, Half–duplex, DTE Remote
I/O
• Odd/even/none parity
DL205 User Manual, 4th Edition, Rev. B
3–8
Chapter 3: CPU Specifications and Operations
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Port 2 Pin Descriptions (DL250–1 / DL260)
1 5V 5 VDC
2 TXD2 Transmit Data (RS-232)
3 RXD2 Receive Data (RS-232)
4 RTS2 Ready to Send (RS–232)
5 CTS2 Clear to Send (RS–232)
6 RXD2 – Receive Data – (RS–422) (RS–485 DL260)
7 0V Logic Ground
8 0V Logic Ground
9 TXD2 + Transmit Data + (RS–422) (RS–485 DL260)
10 TXD2 – Transmit Data – (RS–422) (RS–485 DL260)
11 RTS2 + Request to Send + (RS–422) (RS–485 DL260)
12 RTS2 – Request to Send – (RS–422)(RS–485 DL260)
13 RXD2 + Receive Data + (RS–422) (RS–485 DL260)
14 CTS2 + Clear to Send + (RS422) (RS–485 DL260)
15 CTS2 – Clear to Send – (RS–422) (RS–485 DL260)
Port 2 Pin Descriptions (DL240 only)
1 0V Power (–) connection (GND)
2 5V Power (+) connection
3 RXD Receive Data (RS-232)
4 TXD Transmit Data (RS-232)
5 RTS Request to Send
6 0V Power (–) connection (GND)
6-pin Female
Modular Connector
1
6
15-pin Female
D Connector
1
6
11
5
10
15
ý
þ
ý
ý
230
240
250-1
260
ý
ý
þ
þ
230
240
250-1
260

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com DirectLOGIC DL205 Series and is the answer not in the manual?

Automationdirect.com DirectLOGIC DL205 Series Specifications

General IconGeneral
BrandAutomationdirect.com
ModelDirectLOGIC DL205 Series
CategoryController
LanguageEnglish

Related product manuals