Cable Connections
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 36
J1- Description Internal External
19
Relay
Output 1
Com
20
Relay
Output 1
NO
21
Relay
Output 1
NC
Default
configured as
Fire Alarm
Routing
Equipment.
(FARE)
Potential free
change-over
contact.
Non-
monitored.
Max.
30VDC/1A
22
Relay
Output 2
Com
(non-energized)
23
Relay
Output 2
NO
24
Relay
Output 2
NC
Default
configured as
(FWRE)
Fault Warning
Routing
Equipment.
Potential free
change-over
contact.
Non-
monitored.
Max.30VDC/1
A
25
Detection
Loop1 out +
For connection
of
Max 127
detectors/
loop units
26
Detection
Loop1 out -
27
Detection
Loop1 in +
28
Detection
Loop1 in -
29
Detection
Loop2 out +
For connection
of
Max 127
detectors/
loop units
30
Detection
Loop2 out -
31
Detection
Loop2 in +
32
Detection
Loop2 in -
25
26
27
28
29
30
31
32