Wire shielding should be connected to the power panel .
Notice that the new MM is mounted on an extra mount plate
For connections see drawing ds30008N
Adjustment procedure
• Write down all the parameters of the previous MM.
• connect MM and motor according electrical wiring
• switch on power
• We first make a reset of the parameters by putting :
Parameter 10 = 30
Parameter 970 = 1
• Adjusting of the motorparameters :
Put par10 =1
Possibility to change the motor parameters(p304 to 311) according the parameter list.
When motorparameters are changed store parameters by changing par 3900 = 3
• Adjust the other parameters to the same values of the list or from the previous MM.
Install
Replacement