BENNING IT 130 Measurements
- 58 -
Figure 5.43: Connection of the three-wire test cable in RCD-protected installations
How to perform single-fault leakage current measurements
Set the earthing system according to chapter 4.4.4 to the IT network type.
Select the R
ISO
function by means of the function selector switch.
Set the sub-function to ISFL.
Set the limiting value (optional).
Connect the test cables to the test object (see figure 5.42 and 5.43).
Press the "TEST" key to start the measurement.
Save the measuring result by pressing the "MEM" key (optional).
Figure 5.44: Examples of single-fault leakage current measurements
Results displayed:
Isc1 .......... single-fault leakage current at single fault (earth fault) between L1 and
protective conductor (PE)
Isc2 .......... single-fault leakage current at single fault (earth fault) between L2 and
protective conductor (PE)