BENNING IT 130 Appendix A – Fuse table
- 83 -
Line safety switch, tripping characteristic K
Range of instantaneous tripping: 8 - 14 x I
N
Disconnection time [s
]
35m 0.1 0.2 0.4
Nominal
current
(A)
Minimum prospective short-circuit current (A)
0.5 7.5 7.5 7.5 7.5
1 15 15 15 15
1.6 24 24 24 24
2 30 30 30 30
4 60 60 60 60
6 90 90 90 90
10 150 150 150 150
13 195 195 195 195
15 225 225 225 225
16 240 240 240 240
20 300 300 300 300
25 375 375 375 375
32 480 480 480 480
Line safety switch, tripping characteristic D
Range of instantaneous tripping: 10 - 20 x I
N
Disconnection time [s
]
35m 0.1 0.2 0.4 5
Nominal
current
(A)
Minimum prospective short-circuit current (A)
0.5 10 10 10 10 2.7
1 20 20 20 20 5.4
1.6 32 32 32 32 8.6
2 40 40 40 40 10.8
4 80 80 80 80 21.6
6 120 120 120 120 32.4
10 200 200 200 200 54
13 260 260 260 260 70.2
15 300 300 300 300 81
16 320 320 320 320 86.4
20 400 400 400 400 108
25 500 500 500 500 135
32 640 640 640 640 172.8