EasyManua.ls Logo

Binder vdl 23 - 11 Setting Special Controller Functions; Menu Structure; MB2 Controller; Functions On;Off Menu

Binder vdl 23
235 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VDL (E3) 09/2019 Page 106/234
11. Setting special controller functions
You can set the following functions via the controller menu:
• Activate / deactivate the Standby mode (chap. 9.5)
• Use the optional connection “GAS/AIR2” (10) for ventilation (chap. 11.2)
• Close all existing fine dosing valves (chap. 11.3)
• Turning on / off temperature control (chap. 11.4)
• Turning on / off pressure control (chap. 11.5)
• Starting / terminating the drying monitoring (chap. 11.6)
11.1 Menu structure
11.1.1 MB2 controller
11.1.1.1 “Functions on/off” menu
This chapter describes the setting with operating mode Fixed value operation. Settings for program ope-
ration are described in chap. 18.7.3 (time programs) and chap. 19.6.5 (week programs).
In the “Functions on/off” menu you can define the switching state of three controller functions.
Press the Setpoint setting icon to access the “Setpoint” setting menu from Normal display..
Path: Setpoint > Fixed value operation setpoints > Functions on/off
• Function “ Standby“ (chap. 9.5)
• Function “GAS/AIR 2” (chap. 11.2)
• Function “Close all valves” (chap. 11.3)
“Setpoints” menu.
Select the field “Functions on/off”.
“Functions on/off” entry menu.
Mark / unmark the checkbox to activate / deac-
tivate the desired function and press the Con-
firm icon
The functions are displayed from right to left.
Activated function: switching status “1” (On)
Deactivated function: switching status “0” (Off)

Table of Contents