124 - 8630
PROFIBUS DP
Explanation of the menu items
BUS ADDR Entry of the device address (default: 3)
ADDR xxx
Values from 0 to 126 can be set with the arrow keys;
confirmation is done with the MANUAL/AUTOMATIC key.
BUS PDI Selection of the process values that are to be transferred from the TOP Control
Continuous to the control (master).
* PDI. POS
with the MANUAL/AUTOMATIC key, each process value can be either
: activated (* appears) or deactivated (no * )
* PDI. ERR
For significance of the process values, see table
PDI: Process Data Input
BUS PDO Selection of the process values that are to be transferred from the control
(master) to the TOP Control Continuous.
* PDO. INP
With the MANUAL/AUTOMATIC key, each process value can be either
: activated (* appears) or deactivated (no * ).
* PDO. ERR
For significance of the process values, see table
PDO: Process Data Output
BUS FAIL
Activation for movement to saftey position on bus communication failure
SPOS OFF
The actuator moves to the position corresponding to the setpoint last transmitted
(default setting).
SPOS ON
With
SPOS ON
set, the following configurations can occur:
Activated menu item
SAFEPOS
On error in bus communication, the actuator moves to the position set under
SAFEPOS
.
Deactivated menu item
SAFEPOS
On error in bus communication, the actuator moves to the end position it would
occupy in the zero voltage condition.
Functional deviations from the standard version
The operating mode can be switched between MANUAL and AUTOMATIC in the process operating level
either with the keypad on the TOP Control Continuous or over the bus.
MANUAL/AUTOMATIC switchover on the keypad is no longer possible when an operating mode (under
“PDO MODE”
) is transmitted to the TOP Control Continuous over the bus.