MAINTENANCE AND ERROR CORRECTION ON THE PROCESS CONTROLLER
Other malfunctions
Problem Possible causes Remedy
POS
= 0 (with
CMD
> 0%) or Tight-closing function Deactivate tight-closing
POS
= 100%,(with
CMD
< 100%)
(CUTOFF)
has function
PV
= 0 (with
SP
> 0) or been inadvertently activated
PV = PV
(with
SP
>
SP )
Only with devices with analog
repeat:
red LED
does light Binary output: Check connection of
Current > 100 mA binary output
Binary output does not switch short circuit
Only with devices with process
controller:
Device does not work as a Menu item
P.CONTRL
stands in Remove the menu item
controller despite correctly main menu. The device thus
P.CONTRL
from the main
executed settings. works as a process controller menu.
and expects a process value at
the corresponding input.