8630 - 83
OPERATION AND CONTROLLER FUNCTIONS
CAL.POS
Calibration of the position display (0 - 100 %)
Storage of the minimum position:
Move to minimum position via arrow keys and confirm by pressing the MANUAL / AUTOMATIC key.
Storage of the maximum position:
Move to maximum position via arrow keys and confirm by pressing the MANUAL / AUTOMATIC key.
CAL INP
Calibration of the position setpoint (4 ... 20 mA; 0 ... 20 mA; 0 ... 5 V; 0 ... 10 V)
CAL SP
Calibration of the process setpoint (4 ... 20 mA; 0 ... 20 mA; 0 ... 5 V; 0 ... 10 V)
Menu point does not appear with selection of actual value frequency!
Storage of the minimum input signal (0 mA; 4 mA; 0 V):
Apply the minimum value of the standard signal to the input and confirm ist by pressing the MANUAL/
AUTOMATIC key.
Storage of the maximum input signal (20 mA; 5 V; 10 V):
Apply the maximum value of the standard signal to the input and confirm it by pressing the MANUAL/
AUTOMATIC key.
CAL PV
Calibration of the process setpoint (4 ... 20 mA; Pt-100)
This menu item does not appear on selection of frequency setpoint
Select 4 ... 20 mA:
Apply the minimum value of the process setpoint signal to the input and confirm the value by pressing
the MANUAL/AUTOMATIC key.
Apply the maximum value of the process setpoint signal to the input and confirm the value by pressing
the MANUAL/AUTOMATIC key.
Select Pt-100:
Alter the value displayed using the arrow keys until thedisplay on the SIDE Control S/HART agrees with
that on the reference measuring instrument. Then confirm the value by pressing the MANUAL/
AUTOMATIC key.
NOTE
The signal types
shown in grey
can be selected only with the process controller
activated.
The
signal surrounded by a dotted line
can be selected only with the process
controller deactivated.
The
signal types in brackets
are only shown in this menu; they cannot be
changed here. The type of signal shown is that which you have selected in the
associated menus:
CAL INP (CAL SP)
Display of the selection in the menu
INPUT
CAL PV
Display of the selection in the menu
P.CONTROL
/
P.CO INP
The
signal types over a grey background
can be selected only with the option
flow rate controller.