94 - 8630
OPERATING THE PROCESS CONTROLLER
P.CO - PARA
Parameters of the PID process controller
P.CO - SETP
Type of setpoint setting (internal/external)
Gain factor of the process controller
0 ... 99.99 (factory setting 1.00)
Operating point
0.0 ... 100 % (factory setting 0 %)
Rate time
0 s ... 999.9 s (factory setting 0 s)
Reset time
0.5 s ... 999.9 s (factory setting 999.9 s)
NOTE
For self-optimization of the PID parameters, see Step
The parameters entered should be noted in the table in the Appendix
Tables for process
controller.
For definition of the parameters of a PID controllers, see Appendix
General rules.
Setpoint setting internally via the keys on the TOP
Control
Continuous.
Setpoint setting externally via the standard signal
input.

Table of Contents