750-265 80
0173-017F 0371-
0383
Annunciator 6 configuration R/W See Table 36.
0180-018C 0384-
0396
Annunciator 7 configuration R/W See Table 36.
018D-0199 0397-
0409
Annunciator 8 configuration R/W See Table 36.
019A-01A5 0410-
0421
PII configuration R/W See Table 42.
01A6-01B1 0422-
0433
LCI configuration R/W See Table 42.
01B2-
01BD
0434-
0445
ILK configuration R/W See Table 42t‘g6yv.
01BE-
01BF
0446-
0447
RESERVED
DHW CONFIGURATION
01C0 0448 DHW enable R/W U16 0=DHW disabled
1=DHW enabled
01C1 0449 DHW demand source R/W U16 0=DHW sensor only
1=DHW sensor & Remote Stat
2=DHW switch & inlet sensor
3=DHW switch & outlet sensor
01C2 0450 DHW priority vs CH R/W U16 0=CH > DHW,
1=DHW > CH
01C3 0451 DHW priority vs LL R/W U16 0=LL > DHW,
1=DHW > LL
01C4 0452 DHW priority time R/W U16 0=No DHW priority time,
>0=DHW priority time (min)
01C5 0453 DHW setpoint R/W U16
-40°-130° (0.1°C precision)
1
01C6 0454 DHW time of day setpoint R/W U16
-40°-130° (0.1°C precision)
1
Setpoint when Time Of
Day switch is on.
01C7 0455 DHW on hysteresis R/W U16
-40°-130° (0.1°C precision)
1
01C8 0456 DHW off hysteresis R/W U16
-40°-130° (0.1°C precision)
1
01C9 0457 DHW P-gain R/W U16 0-100
01CA 0458 DHW I-gain R/W U16 0-100
01CB 0459 DHW D-gain R/W U16 0-100
01CC-
01CF
0460-
0463
RESERVED
LIMITS CONFIGURATION
01D0 0464 Outlet high limit setpoint R/W U16
-40°-130° (0.1°C precision)
1
01D1 0465 Outlet high limit response R/W U16 0=Lockout
1=Recycle & hold
01D2 0466 Stack limit enable R/W U16 0=Disable stack limit
1=Enable stack limit
01D3 0467 Stack limit setpoint R/W U16
-40°-130° (0.1°C precision)
1
01D4 0468 Stack limit response R/W U16 0=Lockout
2=Recycle & delay
01D5 0469 Stack limit delay R/W U16 0-600 seconds
01D6 0470 Delta T enable R/W U16 0=Disable Delta T limit
1=Enable Delta T limit
Table 33. CB Falcon Global Modbus Register Map. (Continued)
Address
(hex)
Register
(dec) Parameter
Read/