EasyManua.ls Logo

CleaverBrooks CFC - Page 173

CleaverBrooks CFC
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
750-265 80
0173-017F 0371-
0383
Annunciator 6 configuration R/W See Table 36.
0180-018C 0384-
0396
Annunciator 7 configuration R/W See Table 36.
018D-0199 0397-
0409
Annunciator 8 configuration R/W See Table 36.
019A-01A5 0410-
0421
PII configuration R/W See Table 42.
01A6-01B1 0422-
0433
LCI configuration R/W See Table 42.
01B2-
01BD
0434-
0445
ILK configuration R/W See Table 42t‘g6yv.
01BE-
01BF
0446-
0447
RESERVED
DHW CONFIGURATION
01C0 0448 DHW enable R/W U16 0=DHW disabled
1=DHW enabled
01C1 0449 DHW demand source R/W U16 0=DHW sensor only
1=DHW sensor & Remote Stat
2=DHW switch & inlet sensor
3=DHW switch & outlet sensor
01C2 0450 DHW priority vs CH R/W U16 0=CH > DHW,
1=DHW > CH
01C3 0451 DHW priority vs LL R/W U16 0=LL > DHW,
1=DHW > LL
01C4 0452 DHW priority time R/W U16 0=No DHW priority time,
>0=DHW priority time (min)
01C5 0453 DHW setpoint R/W U16
-40°-130° (0.1°C precision)
1
01C6 0454 DHW time of day setpoint R/W U16
-40°-130° (0.1°C precision)
1
Setpoint when Time Of
Day switch is on.
01C7 0455 DHW on hysteresis R/W U16
-40°-130° (0.1°C precision)
1
01C8 0456 DHW off hysteresis R/W U16
-40°-130° (0.1°C precision)
1
01C9 0457 DHW P-gain R/W U16 0-100
01CA 0458 DHW I-gain R/W U16 0-100
01CB 0459 DHW D-gain R/W U16 0-100
01CC-
01CF
0460-
0463
RESERVED
LIMITS CONFIGURATION
01D0 0464 Outlet high limit setpoint R/W U16
-40°-130° (0.1°C precision)
1
01D1 0465 Outlet high limit response R/W U16 0=Lockout
1=Recycle & hold
01D2 0466 Stack limit enable R/W U16 0=Disable stack limit
1=Enable stack limit
01D3 0467 Stack limit setpoint R/W U16
-40°-130° (0.1°C precision)
1
01D4 0468 Stack limit response R/W U16 0=Lockout
2=Recycle & delay
01D5 0469 Stack limit delay R/W U16 0-600 seconds
01D6 0470 Delta T enable R/W U16 0=Disable Delta T limit
1=Enable Delta T limit
Table 33. CB Falcon Global Modbus Register Map. (Continued)
Address
(hex)
Register
(dec) Parameter
Read/
Write Format Note

Table of Contents

Related product manuals