81 750-265
01D7 0471 Delta T degrees R/W U16
0°-130° (0.1°C precision)
1
01D8 0472 Delta T response R/W U16 0=Lockout
2=Recycle & delay
01D9 0473 Delta T delay R/W U16 0-600 seconds, 0xFFFF=Not configured
01DA 0474 DHW high limit enable R/W U16 0=Disable DHW high limit
1=Enable DHW high limit
01DB 0475 DHW high limit setpoint R/W U16
-40°-130° (0.1°C precision)
1
01DC 0476 DHW high limit response R/W U16 0=Lockout
2=Recycle & hold
3=Suspend DHW
01DD 0477 CH slow start enable R/W U16 0=Disable CH slow start limit
1=Enable CH slow start limit
01DE 0478 DHW slow start enable R/W U16 0=Disable DHW slow start limit,
1=Enable DHW slow start limit
01DF 0479 Slow start ramp R/W U16
RPM/min or %/min
3
01E0 0480 Slow start setpoint R/W U16
-40°-130° (0.1°C precision)
1
01E1 0481 Outlet T-rise limit enable R/W U16 0=Disable Outlet T-rise limit
1=Enable Outlet T-rise limit
01E2 0482 Outlet T-rise degrees R/W U16
Degrees/min (0.1°C precision)
1
01E3 0483 Outlet T-rise delay R/W U16 0-600 seconds, 0xFFFF=Not configured
01E4-
01EF
0484-
0495
RESERVED
ANTICONDENSATION
CONFIGURATION
01F0 0496 CH anticondensation
enable
R/W U16 0=Disable CH anticondensation
1=Enable CH anticondensation
01F1 0497 CH anticondensation
setpoint
R/W U16
-40°-130° (0.1°C precision)
1
01F2 0498 CH anticondensation pump
force off
R/W U16 0=Normal (no change to CH pump)
1=CH pump forced off
01F3 0499 DHW anticondensation
enable
R/W U16 0=Disable DHW anticondensation
1=Enable DHW anticondensation
01F4 0500 DHW anticondensation
setpoint
R/W U16
-40°-130° (0.1°C precision)
1
01F5 0501 DHW anticondensation
pump force off
R/W U16 0=Normal (no change to DHW pump)
1=DHW pump forced off
01F6 0502 Anticondensation priority R/W U16 Is anticondensation more important than (0=No,
1=Yes)? Bit map:
15-5=Reserved (always 0)
4=Outlet high limit
3=Forced rate
2=Slow start
1=Delta T limit
0=Stack limit
01F7-01FF 0503-
0511
RESERVED
OUTDOOR RESET
CONFIGURATION
0200 0512 CH ODR maximum outdoor
temperature
R/W U16
-40°-130° (0.1°C precision)
1
Table 33. CB Falcon Global Modbus Register Map. (Continued)
Address
(hex)
Register
(dec) Parameter
Read/
Write Format Note

Table of Contents

Related product manuals