750-265 92
205 Lead Lag slave was suspended due to fault
206 LL header temperature was invalid
207 Lead Lag was suspended due to no enabled PIM installed
208-221 RESERVED
222 CH frost protection temperature was invalid
223 CH frost protection inlet temperature was invalid
224 DHW frost protection temperature was invalid
225-230 RESERVED
231 LL setpoint was invalid
232 LL time of day setpoint was invalid
233 LL outdoor temperature was invalid
234 LL ODR time of day setpoint was invalid
235 LL ODR time of day setpoint exceeded normal setpoint
236 LL max outdoor setpoint was invalid
237 LL min outdoor setpoint was invalid
238 LL min water setpoint was invalid
239 LL outdoor temperature range was too small
240 LL water temperature range was too small
241-245 RESERVED
246 CH setpoint was invalid
247 CH time of day setpoint was invalid
248 CH outdoor temperature was invalid
249 CH ODR time of day setpoint was invalid
250 CH ODR time of day setpoint exceeds normal
setpoint
251 CH max outdoor setpoint was invalid
252 CH min outdoor setpoint was invalid
253 CH min water setpoint was invalid
254 CH outdoor temperature range was too small
255 CH water temperature range was too small
256-260 RESERVED
261 DHW setpoint was invalid
262 DHW time of day setpoint was invalid
263-274 RESERVED
275 Abnormal Recycle: LCI off during Drive to Purge Rate
276 Abnormal Recycle: LCI off during Measured Purge Time
277 Abnormal Recycle: LCI off during Drive to Lightoff Rate
278 Abnormal Recycle: LCI off during Pre-Ignition test
279 Abnormal Recycle: LCI off during Pre-Ignition time
280 Abnormal Recycle: LCI off during Main Flame Establishing Period
281 Abnormal Recycle: LCI off during Ignition period
282 Abnormal Recycle: Demand off during Drive to Purge Rate
283 Abnormal Recycle: Demand off during Measured Purge Time
284 Abnormal Recycle: Demand off during Drive to Lightoff Rate
285 Abnormal Recycle: Demand off during Pre-Ignition test
286 Abnormal Recycle: Demand off during Pre-Ignition time
Table 39. CB Falcon Alert Codes. (Continued)
Code Description Note