93 750-265
287 Abnormal Recycle: Flame was on during Safe Start check
288 Abnormal Recycle: Flame was on during Drive to Purge Rate
289 Abnormal Recycle: Flame was on during Measured Purge Time
290 Abnormal Recycle: Flame was on during Drive to Lightoff Rate
291 Abnormal Recycle: Flame was not on at end of Ignition period
292 Abnormal Recycle: Flame was lost during Main Flame Establishing Period
293 Abnormal Recycle: Flame was lost early in Run
294 Abnormal Recycle: Flame was lost during Run
295 Abnormal Recycle: Leakage test failed
296 Abnormal Recycle: Interrupted air flow switch was off during Drive to Lightoff Rate
297 Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition test
298 Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition time
299 Abnormal Recycle: Interrupted air flow switch was off during Main Flame
Establishing Period
300 Abnormal Recycle: Ignition failed due to interrupted air flow switch was off
301 Abnormal Recycle: ILK off during Drive to Lightoff Rate
302 Abnormal Recycle: ILK off during Pre-Ignition test
303 Abnormal Recycle: ILK off during Pre-Ignition time
304 Abnormal Recycle: ILK off during Main Flame Establishing Period
305 Abnormal Recycle: ILK off during Ignition period
306-307 RESERVED
308 Run was terminated due to interrupted air flow switch was off
309 Not safe to start due to high limit
310 Drive to Purge Rate failed due to high limit
311 Measured Purge Time failed due to high limit
312 Drive to Lightoff Rate failed due to high limit
313 Pre-Ignition test failed due to high limit
314 Pre-Ignition time failed due to high limit
315 Main Flame Establishing Period failed due to high limit
316 Ignition failed due to high limit
317 Run was terminated due to high limit
318 Stuck reset switch
319-360 RESERVED
361 Internal error: No factory parameters were detected in control
362 Internal error: PID iteration frequency was invalid
363 Internal error: Demand-Rate interval time was invalid
364 Internal error: Factory calibration parameter for modulation was invalid
365 Internal error: CH PID P-scaler was invalid
366 Internal error: CH PID I-scaler was invalid
367 Internal error: CH PID D-scaler was invalid
368 Internal error: DHW PID P-scaler was invalid
369 Internal error: DHW PID I-scaler was invalid
370 Internal error: DHW PID D-scaler was invalid
371 Internal error: Lead Lag master PID P-scaler was invalid
372 Internal error: Lead Lag master PID I-scaler was invalid
373 Internal error: Lead Lag master PID D-scaler was invalid
Table 39. CB Falcon Alert Codes. (Continued)
Code Description Note

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CleaverBrooks CFC and is the answer not in the manual?

CleaverBrooks CFC Specifications

General IconGeneral
BrandCleaverBrooks
ModelCFC
CategoryBoiler
LanguageEnglish

Related product manuals