833-3577 CB-FALCON SYSTEM OPERATOR INTERFACE
750-241 21 65-0296—01
Stack Limit Configuration Parameters
Table 13 displays stack limit configuration parameters.
Fig. 40. Stack Limit configuration.
Other Limit Configuration Parameters
Table 14 displays other limit parameters.
Fig. 41. Other Limit configuration.
Table 13. Stack Limit Configuration Parameters.
Parameter Comment
Stack limit Enabled
Disabled
Stack limit delay 0-600 seconds
Stack limit response Lockout
Recycle & delay
Stack limit setpoint -40 °C - 130 °C (-40 °F - 266 °F)
Table 14. Other Limit Configuration Parameters.
Parameter Comment
Delta-T limit enable Enabled
Disabled
Delta-T limit delay 0-600 seconds
Delta-T limit
response
Recycle & delay
Lockout
Delta-T limit degrees -40 °C - 130 °C (-40 °F - 266 °F)
Outlet T-rise limit
enable‘
Enabled
Disabled
Outlet T-rise degrees -40 °C - 130 °C (-40 °F - 266 °F)
Outlet T-rise delay 0-600 seconds