833-3577 CB-FALCON SYSTEM OPERATOR INTERFACE
65-0296—01 22 750-241
Anti-Condensation Configuration Parameters
Table 15 displays anti-condensation parameters.
Fig. 42. Anti-condensation configuration.
Frost Protection Parameters
Table 16 displays frost protection parameters.
Fig. 43. Frost Protection configuration.
Table 15. Anti-Condensation Configuration Parameters.
Parameter Comment
CH anticondensation
enable
Enabled
Disabled
CH anticondensation
pump
Normal (no change)
CH pump forced off
CH anticondensation
setpoint
-40 °C - 130 °C (-40 °F - 266 °F)
DHW
anticondensation
enable
Enabled
Disabled
DHW
anticondensation
pump
Normal (no change)
DHW pump forced off
DHW
anticondensation
setpoint
-40 °C - 130 °C (-40 °F - 266 °F)
Anticondensation
priority
Is anticondensation more important
than (0=No, 1=Yes)?
Bit map:
15-5=Reserved (always 0)
4=Outlet high limit
3=Forced rate
2=Slow start
1=Delta-T limit
0=Stack limit
Table 16. Frost Protection Configuration Parameters.
Parameter Comment
CH frost protection
enable
Enabled
Disabled
DHW frost protection
enable
Enabled
Disabled
Outdoor frost
protection setpoint
-40 °C - 130 °C (-40 °F - 266 °F)
(applicable for CH only)