EasyManuals Logo

CleaverBrooks ProtoNode User Manual

CleaverBrooks ProtoNode
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
ProtoNode Gateway
750-426 11
2.3 Configuring Device Communications
2.3.1 Input COM Setting s on all Seria l De vice s C onnected to the Proto Node
All of the connected serial devices MUST have the same Baud Rate, Data Bits, Stop Bits, and Par-
ity settings as the ProtoNode.
Figure 5 specifies the device serial port settings required to communicate with the ProtoNode.
FIGURE 5 - COM Settings
2.3.2 Set Modbus Node-ID for each device attached to the ProtoNode
Set Modbus Node-ID for each of the devices attached to ProtoNode. The Modbus Node-ID's need to
be uniquely assigned between 1 and 255. The Modbus Node-ID that is assigned for each device
needs to be documented. The Modbus Node-IDs assigned are used for designating the Device
Instance for BACnet/IP and BACnet MS/TP (Section 2.5.2)
The Metasys N2 and Modbus TCP/IP Field Protocol Node-IDs are automatically set to the same
value as the Node-ID of the device.
2.3.3 Set IP Address for each Ethernet Device Connected to the ProtoNode
Ensure devices are set to Modbus TCP/IP to communicate with the ProtoNode.
The device needs to be on the same IP subnet as the ProtoNode and the configuration PC.
Record the following device information to start the setup:
IP Address
IP port
Node-ID
NOTE: This information is required for Section 4.
2.4 Selecting the Desired Field Protocol
NOTE: If using the ProtoNode only for cloud-based data monitoring, Sections 2.4 and 2.5 may be
skipped.
ProtoNode RER units use the “S” bank of DIP switches (S0 - S2) to select the Field Protocol.
See Figure 6 for the DIP switch settings.
The OFF position is when the DIP switches are set closest to the outside of the box.
ProtoNode LER units do not use the “S” bank DIP switches to select a Field Protocol. On ProtoNode LER
units, these DIP switches are disabled; the Field Protocol is always LonWorks.
Port Setting Falcon Steam & Hydronic
Other Serial Devices
Protocol Modbus RTU Modbus RTU
Baud Rate 38400 9600
Parity None None
Data Bits 8 8
Stop Bits 1 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CleaverBrooks ProtoNode and is the answer not in the manual?

CleaverBrooks ProtoNode Specifications

General IconGeneral
BrandCleaverBrooks
ModelProtoNode
CategoryGateway
LanguageEnglish