2. Write the command argument into the registers 44208-44209 (register addresses 4207-4208). Use function
16.
3. Write the command code into the register 44210 (register address 4209). Use function 6.
4. (Optional) Read the command return value from the registers 44208-44209 (register addresses 4207-4208).
Use function 3.
5. If the command was executed the return value is as listed in the table. If the command was accepted but
there was an error during execution the return value indicates the reason:
a. 0x00000001 invalid argument
b. 0x00000002 command refused (e.g. controller not in MAN, breaker can not be closed in the specific
situation etc.)
Action Command code Argument Return value
Engine start *) 0x01 0x01FE0000 0x000001FF
Engine stop *) 0x01 0x02FD0000 0x000002FE
Fault reset *) 0x01 0x08F70000 0x000008F8
Horn reset *) 0x01 0x04FB0000 0x000004FC
GCB toggle *) 0x02 0x11EE0000 0x000011EF
GCB on 0x02 0x11EF0000 0x000011F0
GCB off 0x02 0x11F00000 0x000011F1
MCB toggle *) 0x02 0x12ED0000 0x000012EE
MCB on 0x02 0x12EE0000 0x000012EF
MCB off 0x02 0x12EF0000 0x000012F0
*) This action is an equivalent of pressing the front panel button