InteliLite 9 Global Guide
368
Alarm Type Warning
Alarmlist message Override All Sd
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm occurs when binary input SD OVERRIDE (PAGE 313) is activated.
Wrn Override All Sd
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Stop Fail
Alarm evaluated While the engine shall be stopped
Related applications AMF, MRS
Description
This alarm occurs if the gen-set shall be stopped, but some symptom indicates that
it is not stopped. The period when the gen-set shall be stopped begins after the
FUEL SOLENOID (PAGE 326) has been switched off and time delay Stop Time (page
176) has elapsed and lasts for the entire time the FUEL SOLENOID (PAGE 326) or
STARTER (PAGE 344) are off.
Image 9.1 Stop Fail
Note: Gen-set cannot be started until this alarm is inactive and reset.
Wrn Stop Fail
6 back to List of alarms level 1
Other type
Alarm Type Alarm indication
Alarmlist message After-Treatment
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm occurs when appropriate after-treatment lamp is active.
After-Treatment
6 back to List of alarms level 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 9 and is the answer not in the manual?

ComAp InteliLite 9 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 9
CategoryController
LanguageEnglish

Related product manuals