Setpoint group AMF settings Related FW 1.1.0
Range [units]
50 .. Mains Overvoltage (page 202) [%]
Default value 60 % Alternative config YES
Step
1 % of Nominal Voltage Ph-Ph (page 149)
Comm object 8307 Related applications AMF
Config level Standard
Setpoint visibility
Conditioned by the setpoint Operation Mode (page 154)
Description
Threshold for mains undervoltage. All three phases are checked. Minimum voltage out of three phases is
used.
Mains Undervoltage
6 back to List of setpoints
Setpoint group AMF settings Related FW 1.1.0
Range [units] 0,0 .. 600,0 [s]
Default value 2,0 s Alternative config YES
Step 0,1 s
Comm object 8306 Related applications AMF
Config level Standard
Setpoint visibility
Conditioned by the setpoint Operation Mode (page 154)
Description
Delay for Mains Undervoltage (page 203) and Mains Overvoltage (page 202) protection.
Mains < > Voltage Delay
6 back to List of setpoints
Subgroup: AMF Frequency Conditions
Setpoint group AMF settings Related FW 1.1.0
Range [units]
Mains Underfrequency (page 204) .. 150 [%]
Default value 102,0 % Alternative config NO
Step
1,0 % of Nominal Frequency (page 150)
Comm object 8310 Related applications AMF
Config level Standard
Setpoint visibility
Conditioned by the setpoint Operation Mode (page 154)
Description
Threshold for mains overfrequency.
Mains Overfrequency
6 back to List of setpoints