InteliLite 9 Global Guide
375
Related applications AMF, MRS
Description
This alarm occurs when an ECU is configured, but the communication with the
ECU is not established or has dropped out.
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Fuel Level
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the fuel level is lower than the level set in Fuel Level Sd
(page 184) setpoint.
Sd Fuel Level
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd GCB Fail
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm will occur when the GCB FEEDBACK (PAGE 307) input does not match
the expected position given by the GCB CLOSE/OPEN (PAGE 327) output. It stays
active until the mismatch between the output and feedback persists.
If there was no command issued by the controller and the breaker
(feedback) changes suddenly the position itself, the alarm will be issued
immediately.
The alarm will be also issued if the breaker does not respond to an open or
close command within 5 seconds.
Sd GCB Fail
6 back to List of alarms level 2
Alarm Type Sd
Alarmlist message Sd + Name of analog input
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that value the general analog protection is out of shutdown
protection limit.
Sd AIN Protec
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd + Name of binary input
Alarm evaluated All the time
Sd BIN Protection