EasyManua.ls Logo

ComAp InteliLite 9 - AL AIN 3 Wrn; AL Battery Flat; AL Battery Overvoltage; AL Battery Undervoltage

ComAp InteliLite 9
401 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite 9 Global Guide
317
Related FW 1.1.0 Related applications AMF, MRS
Comm object 1384
Description
The output is closed when there is the warning alarm from the analog input 3 of the controller present in the
alarmlist or isnt confirmed.
AL AIN 3 Wrn
6 back to Logical binary outputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 1292
Description
This output is active when the Sd Battery Flat (page 374) or Wrn Battery < Voltage (page 359) alarm is
present in the alarmlist or isn’t confirm.
AL Battery Flat
6 back to Logical binary outputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 1995
Description
This output is active when the Wrn Battery > Voltage (page 359) alarm is present in the alarmlist or isn’t
confirm.
AL Battery Overvoltage
6 back to Logical binary outputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 1994
Description
This output is active when the Wrn Battery < Voltage (page 359) alarm is present in the alarmlist or isn’t
confirm.
AL Battery Undervoltage
6 back to Logical binary outputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 1293
Description
This output is active when the Wrn Battery > Voltage (page 359) or Wrn Battery < Voltage (page 359)
alarm is present in the alarmlist or isn’t confirm.
AL Battery Voltage
6 back to Logical binary outputs alphabetically

Table of Contents