InteliLite 9 Global Guide
181
Setpoint group Engine settings Related FW 1.1.0
Range [units] the range is defined by ECU sensor curve
Default value
the value is defined by
ECU sensor curve
Alternative config NO
Step the step is defined by ECU sensor curve
Comm object 14425 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if ECU is configured
Description
Shutdown threshold level for Oil pressure which is send from ECU.
ECU Oil Pressure Sd
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0 .. 900 [s]
Default value 3 s Alternative config NO
Step 1 s
Comm object 14427 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if ECU is configured
Description
Delay for Oil pressure which is send from ECU.
ECU Oil Pressure Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 12896 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input COOLANT TEMP (PAGE 353) is configured
Description
Warning or history threshold level for COOLANT TEMP (PAGE 353).
Coolant Temperature Wrn
6 back to List of setpoints