Setpoint group Engine settings Related FW 1.1.0
Range [units] 0 .. 3 600 [s]
Default value 180 s Alternative config NO
Step 1 s
Comm object 8662 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Runtime of engine after cooling pump. Binary output Cooling pump is closed when the engine starts and
opens AfterCool time delayed after gen-set stops.
After Cooling Time
6 back to List of setpoints
Subgroup: Engine Protections
Setpoint group Engine settings Related FW 1.1.0
Range [units]
Underspeed Sd (page 178)50 .. 200 [%]
Default value 115% Alternative config NO
Step
1 % of Nominal RPM (page 151)
Comm object 8263 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for over speed protection. Relative to the nominal speed.
Overspeed Sd
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units]
0 .. Overspeed Sd (page 178) [%]
Default value 25% Alternative config NO
Step
1 % of Nominal RPM (page 151)
Comm object 8260 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for underspeed protection. Relative to the nominal speed.
Underspeed Sd
6 back to List of setpoints