Setpoint group Engine settings Related FW 1.1.0
Range [units] the range is defined by ECU sensor curve
Default value
the value is defined by
ECU sensor curve
Alternative config NO
Step the step is defined by ECU sensor curve
Comm object 14428 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if ECU is configured
Description
Shutdown or BOC threshold level for Coolant temperature which is send from ECU.
ECU Coolant Temperature Sd
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0 .. 900 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 14430 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if ECU is configured
Description
Delay for Coolant temperature which is send from ECU.
ECU Coolant Temperature Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config YES
Step the step is defined by analog sensor curve
Comm object 9684 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if the logical analog input COOLANT TEMP (PAGE 353) is configured
Description
Threshold level for lower limit of COOLANT TEMP (PAGE 353).
Coolant Temperature Low Wrn
6 back to List of setpoints