EasyManua.ls Logo

ComAp InteliLite 9 - Event SMS 1 Fail; Wrn Battery Voltage; Wrn Charging Alternator Fail

ComAp InteliLite 9
401 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite 9 Global Guide
359
Alarm Type Other
Alarmlist message Event SMS1 Fail
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm indicates that there was a request to send an event SMS to telephone
number which is adjusted in setpoint Telephone Number 1 (page 230) and SMS
wasn’t send.
Event SMS1 Fail
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message All the time
Alarm evaluated Wrn Battery > Voltage
Related applications AMF, MRS
Description
This alarm informs the operator that the controller supply voltage is too high. The
following setpoints are related to it:
Battery Overvoltage (page 188)
Battery <> Voltage Delay (page 189)
Wrn Battery > Voltage
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Battery < Voltage
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm informs the operator that the controller supply voltage is too low. The
following setpoints are related to it:
Battery Undervoltage (page 188)
Battery <> Voltage Delay (page 189)
Wrn Battery < Voltage
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Charging Alternator Fail
Alarm evaluated Engine running only
Related applications AMF, MRS
Description
This alarm is issued if the engine is running and the voltage on the D+ terminal is
lower than D+ Treshold (page 170) of the controller supply voltage. This alarm
works similar to the red battery” alarm indicator on a vehicle dashboard.
The setpoint has to be in Charge Fail or Enabled position to enable this alarm.
Wrn Charging Alternator Fail
6 back to List of alarms level 1