InteliLite 9 Global Guide
175
Setpoint group Engine settings Related FW 1.1.0
Range [units]
Minimal Stabilization Time (page 174) .. 300 [s]
Default value 10 s Alternative config NO
Step 1 s
Comm object 8313 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
When the gen-set has been started and the idle timer has elapsed, the generator voltage and frequency must
get within limits within this period of time, otherwise an appropriate shutdown alarm (generator voltage and/or
frequency) is issued.
Image 8.10 Maximal Stabilization Time
Maximal Stabilization Time
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0,0 .. 300,0 [s]
Default value 5,0 s Alternative config YES
Step 0,1 s
Comm object 10023 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
During the start of the gen-set, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the Protect Hold Off. The time starts after reaching Starting RPM.
Protection Hold Off
6 back to List of setpoints