InteliLite 9 Global Guide
205
Setpoint group AMF settings Related FW 1.1.0
Range [units] Manual / Auto [-]
Default value Manual Alternative config NO
Step [-]
Comm object 8618 Related applications AMF
Config level Advanced
Setpoint visibility
Conditioned by the setpoint Operation Mode (page 154)
Description
Setpoint adjust the behavior of test mode.
Manual 1. Select TEST mode, gen-set will start and run unloaded
2.
To transfer the load from mains to gen-set press MCB button or wait for mains
fail
3. The gen-set remains running loaded when mains recovers
4. To transfer load back to mains press MCB button or switch controller to AUTO
mode (mains has to be healthy)
5. To stop the gen-set switch controller to AUTO (to stop gen-set automatically) or to
MAN mode (to stop gen-set manually)
Auto 1. Select TEST mode, gen-set will start and run unloaded
2. To transfer load from mains to the gen-set wait for the mains fail. The controller
does not response for MCB button .
3. When the mains recovers:
a.
After the Mains Return Delay (page 200) the controller opens the GCB
b.
After the Transfer Delay (page 201) the controller closes the MCB
4. The gen-set remains running unloaded
5. To stop the gen-set switch controller to AUTO (to stop gen-set automatically) or to
MAN mode (to stop gen-set manually)
Return From Test
6 back to List of setpoints
Setpoint group AMF settings Related FW 1.1.0
Range [units] Close On / Close Off [-]
Default value Close Off Alternative config NO
Step [-]
Comm object 8444 Related applications AMF
Config level Advanced
Setpoint visibility
Conditioned by the setpoint Operation Mode (page 154)
Description
The set point influences the behavior of the output MCB CLOSE/OPEN (PAGE 335).
Close On When the output MCB CLOSE/OPEN (PAGE 335) is closed – MCB should be closed.
MCB Logic