InteliLite 9 Global Guide
370
Related applications AMF, MRS
Description
The controller detects phase sequence on generator voltage terminals. This
protection is important after controller installation to avoid wrong voltage phase
connection. There is a fixed defined phase sequence in InteliLite 9 controller: T35 =
N, T36 = L1, T37 = L2 and T38 = L3. When the phases are connected in a different
order, alarms are detected. This alarm prevent circuit breaker closing.
6 back to List of alarms level 1
Alarm Type Alarm indication
Alarmlist message Mains CCW Rotation
Alarm evaluated All the time
Related applications AMF
Description
The controller detects phase sequence on mains voltage terminals. This protection
is important after controller installation to avoid wrong voltage phase connection.
There is a fixed defined phase sequence in InteliLite 9 controller: T39 = N, T40 =
L1, T41 = L2 and T42 = L3. When the phases are connected in a different order,
alarms are detected. This alarm prevent circuit breaker closing.
Mains CCW Rotation
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Manual Restore
Alarm evaluated All the time
Related applications AMF
Description
Alarm is activated when controller is in AUTO mode, Return From Island (page 204)
setpoint is set to manual, load is on gen-set a mains has returned.
Manual Restore
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message Module(slotA) - comm. outage
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with communication between controller
and module in slot.
Module(slotA) - comm. outage
6 back to List of alarms level 1