Password
This password is the same as in InteliConfig or directly in controller.
Table Reserved registers (page 127)
Register addresses Number of registers Access Data type Meaning
4211 1 write Unsigned16 Password
Note: Default password is "0".
In this example the password is "1234".
Request: (Numbers in Hex)
01 06 10 73 04 D2 7C D1
Controller address Modbus function
Register address
1073
hex
= 4211
dec
Password
04D2
hex
= 1234
dec
CRC
Response for success: (Numbers in Hex)
01 06 10 73 00 00 7C D1
Controller address Modbus function
Register address
1073
hex
= 4211
dec
Allways zero. CRC
Response for bad password: (Numbers in Hex)
01 86 04 43 A3
Controller
address
Modbus exception
for function 6.
04 – device error
see Error codes (exception codes) on page 127
CRC