InteliLite 9 Global Guide
253
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0 .. 100 [%]
Default value 50 % Alternative config NO
Step 1 %
Comm object 14337 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.
Note: This value is used when any other alternate configuration is not active.
ECU Speed Adjustment 1