EasyManuals Logo
Home>ComAp>Controller>InteliLite 9

ComAp InteliLite 9 User Manual

ComAp InteliLite 9
401 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #257 background imageLoading...
Page #257 background image
InteliLite 9 Global Guide
257
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0 .. 100 [%]
Default value 50 % Alternative config NO
Step 1 %
Comm object 15199 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 295) is active.
ECU Speed Adjustment 3
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 9 and is the answer not in the manual?

ComAp InteliLite 9 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 9
CategoryController
LanguageEnglish

Related product manuals