InteliLite 9 Global Guide
364
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phase 3. The following
setpoints are related to it:
Generator Undervoltage Wrn (page 194)
Generator <> Voltage Delay (page 195)
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator L3L1 > Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 3 and
1. The following setpoints are related to it:
Generator Overvoltage Wrn (page 194)
Generator <> Voltage Delay (page 195)
Wrn Generator L3L1 > Voltage
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator L3L1 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 3 and
1. The following setpoints are related to it:
Generator Undervoltage Wrn (page 194)
Generator <> Voltage Delay (page 195)
Wrn Generator L3L1 < Voltage
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator > Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Overfrequency Wrn (page 195)
Generator <> Frequency Delay (page 196)
Wrn Generator > Frequency
6 back to List of alarms level 1