InteliLite 9 Global Guide
379
Alarm Type Shutdown
Alarmlist message Sd Generator L3L1 > Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 3 and
1. The following setpoints are related to it:
Generator Overvoltage Sd (page 193)
Generator <> Voltage Delay (page 195)
Sd Generator L3L1 > Voltage
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Generator L3L1 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 3 and
1. The following setpoints are related to it:
Generator Undervoltage BOC (page 194)
Generator <> Voltage Delay (page 195)
Sd Generator L3L1 < Voltage
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Generator > Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Overfrequency BOC (page 195)
Generator <> Frequency Delay (page 196)
Sd Generator > Frequency
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Generator < Frequency
Alarm evaluated Generator excited only
Sd Generator < Frequency