InteliLite 9 Global Guide
76
25% Nominal voltage
Maximum Cranking Time (page
160)
, 1st attempt
STARTER (PAGE 344) off, FUEL
SOLENOID (PAGE 326) off, STOP
SOLENOID (PAGE 345)
on,
Cranking
Fail Pause (page 160)
timer started
Crank
pause
Maximum Cranking Time (page 160)
elapsed, last attempt
STARTER (PAGE 344) off, PRESTART
(PAGE 341) off
Shutdown
(Start fail)
Crank pause
Cranking Fail Pause (page 160)
elapsed
STARTER (PAGE 344) on, FUEL
SOLENOID (PAGE 326) on, STOP
SOLENOID (PAGE 345)
off,
Maximum
Cranking Time (page 160)
counter
started
Cranking
Starting
Idle Time (page 172)
elapsed
Minimal Stabilization Time (page 174)
and
Maximal Stabilization Time (page
175)
counter started
Running
any shutdown condition FUEL SOLENOID (PAGE 326) off,
STOP SOLENOID (PAGE 345) on
Shutdown
all cranking attempts elapsed FUEL SOLENOID (PAGE 326) off,
STOP SOLENOID (PAGE 345) on
Shutdown
(Start fail)
Running Stop request READY TO LOAD (PAGE 343)
off,
Cooling Time (page 176)
counter
started
Cooling
RPM = 0 or any other shutdown
condition
READY TO LOAD (PAGE 343) off,
FUEL SOLENOID (PAGE 326) off
Shutdown
GCB CLOSE/OPEN (PAGE 327)
closed
Loaded
Loaded GCB CLOSE/OPEN (PAGE 327)
opened
Running
RPM = 0 or any other shutdown
condition
FUEL SOLENOID (PAGE 326) off,
STOP SOLENOID (PAGE 345) on,
READY TO LOAD (PAGE 343) off,
Shutdown
Cooling
Cooling Time (page 176)
elapsed
FUEL SOLENOID (PAGE 326) off,
STOP SOLENOID (PAGE 345) on
Stop
RPM = 0 or any other shutdown
condition
FUEL SOLENOID (PAGE 326) off,
STOP SOLENOID (PAGE 345) on
Shutdown
Start request READY TO LOAD (PAGE 343) on Running
Stop RPM = 0, Oil pressure not
detected, Generator voltage < 10V,
D+ not active
Ready
If at least one of engine running
indication is detected when
Stop
Time (page 176)
elapsed.
Stop (Stop
fail)