InteliLite Global Guide
189
Setpoint group Engine settings Related FW 1.9.0
Range [units] Diesel / Gas [-]
Default value Diesel Alternative config NO
Step [-]
Comm object 9100 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Determines behavior of the Binary output FUEL SOLENOID (PAGE 572)
Diesel: Output closes before binary output STARTER (PAGE 597). Lead of output is adjusted via
setpoint Fuel Solenoid Lead (page 198). The output opens if Emergency Stop comes
or gen-set is stopped and in pause between repeated starts.
Gas:
(Gaseous)
Output closes together with binary output IGNITION (PAGE 582) if RPM is over the 30
RPM (fixed value). Output opens after stop command or in pause between repeated
start.
Fuel Solenoid
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 1 .. 10 [-]
Default value 3 Alternative config NO
Step 1
Comm object 8255 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maximal number of cranking attempts.
Cranking Attempts
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
BrandComAp
ModelInteliLite AMF25
CategoryController
LanguageEnglish

Related product manuals