InteliLite Global Guide
98
5.5 Functions
5.5.1 Start-stop sequence 98
5.5.2 AMF sequence 100
5.5.3 Operating Modes 101
5.5.4 Engine start 102
5.5.5 Stabilization 107
5.5.6 Connecting to load 107
5.5.7 MRS operation 107
5.5.8 AMF operation 107
5.5.9 Dual Operation 109
5.5.10 Engine cool down and stop 112
5.5.11 Alarm management 112
5.5.12 History log 118
5.5.13 Breaker control 120
5.5.14 Exercise timers 123
5.5.15 Rental Timers 129
5.5.16 Service timers 130
5.5.17 Analog switches 130
5.5.18 Additional running engine indications 132
5.5.19 Voltage phase sequence detection 132
5.5.20 Gen-set operation states 133
5.5.21 Sensor curves 135
5.5.22 PLC 137
5.5.23 Geo-fencing 144
5.5.24 Tier 4 Final 144
5.5.25 Alternate configuration 147
5.5.26 ECU Frequency selection 148
5.5.27 Cybernetic security 148
6 back to Controller setup
5.5.1 Start-stop sequence
State Condition of the transition Action Next state
Ready Start request PRESTART (PAGE 621) on Prestart
Time (page 207) counter started
Prestart
RPM > 2 or Oil pressure > Starting
Oil Pressure (page 208) or
Generator voltage > 10V or D+
voltage is higher than D+ Treshold
(page 222)
Stop (Stop
fail)
OFF Mode selected or Shutdown
alarm active
Not Ready