4. DatainReport:Oneormoreofthegainvaluesexceeds3.0.
l
Interpretation:Bearingelectricalfaultorshaftisobstructed
l
Action:Verifythebearings
l
Action:Verifythebearingsensors
RefertoFigure5-3BearingCalibrationFlowonpage268.
5. DatainReport:OneormoreofthebearingForceCurrentvaluesexceeds1.5AinValidationResults.
l
Interpretation:Bearingelectricalfaultorshaftisobstructed
l
Action:Verifythebearings
l
Action:Verifythebearingsensors
RefertoFigure1-3BearingCalibrationFlowonpage1.
6. DatainReport:Thedifferencebetweenthe“LatestCalibration”and“StoredCalibration”isgreaterthan
30percent.
l
Interpretation:Bearing/Shaftpositionhaschangedfromstoredtolatest
l
Action:SavetoEEPROMandcyclepower;testruncompressorwithnewvalues
l
Action:Verifythebearings
l
Action:Verifythebearingsensors
RefertoFigure5-3BearingCalibrationFlowonpage268.
M-SV-001-EN Rev. H-1/23/2023 Page 267 of 294